Article code
TPU 43.23
Description
**(customer-specific goods are excluded from return (exchange, return))
Current Transformer
CT type: TPU 43.23
Ratio: 1250/1/1A
Standard:IEC 61869-2
Insulation level: 7.2/20/60kV
Frequency: 60Hz
Ith: 40(1s) na
Idynes: 100 kA
Ambient temperature: 40 °C
Altitude: 1000m
Core 1: 1S1-1S2
Ratio: 1250/1A
Accuracy class: 0.5 p
Burden: 10VA
fs: 10
Rct: 6 ohms
External: 120%
Core 2: 2S1-2S2
Ratio: 1250/1A
Accuracy class: 5P30
Burden: 10VA
Rct: 8 ohms
External: 120%
Additional optio
YOUR ENQUIRY